Cellcorder Standby
Battery Test Meter
This is a high tech unique portable battery test
instrument, which displays and automatically records cell
voltages together with internal cell and cell connector resistance.
The system also includes the leading 'Battery
Analysis' software.

Critical standby power battery backed installations need to
perform instantly when called upon during an outage. To ensure
maximum reliability from the considerable investment made
a number of rules should be observed. Once installation has
been completed, the battery must be commission charged and
a full autonomy discharge/recharge cycle test undertaken to
establish the 'as new' performance. Prior to undertaking this
discharge it is advisable to ensure that all terminations
are tight, torqued up to the manufacturers recommended settings
and individual cell voltages inter-cell resistance and internal
resistance's are logged.
This task is speedily completed and the data recorded by using
the CTL 500 Cellcorder Standby Battery Test Multimeter.
Previously only recordable using three separate instruments,
these readings are critical as they will form the base parameters
against which decisions will be taken to determine that useful
service life has been reached. By periodic testing with the
Cellcorder, using its inbuilt short duration DC load capability
and without taking the battery off-line , a data series is
established. Utilising the supplied software conveniently
turns the tabular data into easy to read graphical trends.
Automatic comparison against user definable alarm levels rapidly
identifies any cells/blocks becoming a potential cause of
failure.
When vented batteries are in service the Specific Gravity
readings and temperatures are taken with our CTL-200
Hydrostik Digital Data logging Hydrometer/Thermometer.
This data can be inputted to provide the most complete effort
free reports.
All instrumentation must be maintained within calibration,
CellCare Technologies will send a reminder annually to ensure
it is not forgotten. A traceable accredited certificate of
conformance
is issued.
Housed in a protective, padded, shoulder fitting carrying
case, with an easy to read display and user friendly keypad
the CTL 500 Cellcorder represents the state of the art in
Portable Battery Diagnostic Test Instrumentation.
It has two modes of operation, usable as a Voltmeter only, or in 'Multimeter.'
setting, applying a short duration load.
'Power Cord Free' operation is provided by a rechargeable battery, giving up
to 6 hours usage between recharges.
Automatic Power Saving features are included which ensure consumption is minimised.
The method is tried and trusted by the most discerning users
to give accurate reliable information against which to make
critical judgments on cell conditions.
CellCare Technologies also provides unbiased advice to users
to help them in their decision making.
The unit comes complete with all necessary cables and fully insulated quick
release clips.
|
|
- Float Voltage Readings
The Cellcorder measures the voltage applied during full
float operation. The voltage range covers all cell or modules
up to 16 volts. Cell or module reading accuracy is to four
full digits.
- Internal Cell Resistance
The internal resistance of a cell can be determined by how
that cell responds to a momentary load. the instantaneous
voltage drop and load current applied are used to calculate
the resistance. Cellcorder algorithms make this measurement
possible on cells floating on-line or off-line.
- Inter Cell Resistance
The Cellcorder measures the resistance between two cell
terminals that are electrically connected. The measurement
consists of the connector resistance and the contact resistance
at the points of connection to the cell terminals.
- Auto Ranging
The Cellcorder automatically selects the correct voltage
range, load resistor and time for a test.
- Data Extraction and Analysis
After all testing is completed; the Cellcorder can be connected
via an RS232 port to a computer. The data extraction program
analyses the test data and displays results in a bar graph
or tabulated format. A test report may be printed or saved
to a file. This file can be exported in an ASCII or
comma-delimited format to allow off-the-shelf programs or
supplied Battery
Analysis trending software to generate customized reports.